Chapter2 Connection to a PLC
2-150
(*2) Address selection rule is as follows.
WindO/I-NV2 uses 32 bit device as the divided 2 word device.
Therefore, the last one digit shows that the device is upper word or lower word.
Standard device address format of WindO/I-NV2
REAL
2552551
ControlLogix Address --- REAL 123:255
WindO/I-NV2 Address --- REAL 1232550 or F1232551
3 di
g
its Element number
3 di
g
its File number
1 digits 0: Lower word 1: Upper word
Allen-Bradley device address format
REAL
255
:
255
_
3 di
g
its Element number
3 di
g
its File number
1 digits 0: Lower word 1: Upper word